RESOLUTION NO. 8296
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF
VERNON APPROVING AND AUTHORIZING NOTICE INVITING
SEALED PROPOSALS OR BIDS FOR THE PURCHASE OF A SF6
GAS VAULT SWITCH FOR THE LIGHT & POWER DEPARTMENT
WHEREAS, the Light & Power Department is in need of a Sulfur
Hexafluoride (SF6) gas vault switch (the "SF6 Switch") to be used as a
spare at the Farmer John facility; and
WHEREAS, on October 14, 2003, the Finance Committee
considered the recommendation of Bruce V. Malkenhorst, Director of
Finance, dated October 2, 2003, that authority be granted for the
Purchasing Agent, or his designee, to seek formal bids for the
purchase of the SF6 Switch; and
WHEREAS, Specification No. GSI-2003 (the "Specification")
has been prepared for the purchase of the SF6 Switch; and
WHEREAS, the City Council of the City of Vernon has
determined that it is in the best interests of the City of Vernon that
bids or proposals be solicited in accordance with applicable State law
and the Vernon City Code.
NOW, THEREFORE, BE IT RESOLVED BY THE CITY COUNCIL OF THE
CITY OF VERNON AS FOLLOWS:
SECTION l: The City Council of the City of Vernon hereby
finds and determines that the recitals contained hereinabove are true
and correct.
SECTION 2: The Specification, a copy of which is attached
hereto as Exhibit "A" and made a part hereof, is hereby approved by
the City Council of the City of Vernon.
SECTION 3: The City Clerk of the City of Vernon, or his
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
designee, is hereby directed to give notice, in writing, inviting
sealed proposals or bids for the purchase of the SF6 Switch in
accordance with the Specification, and in accordance with this
resolution.
SECTION 4: There being no newspaper of general circulation
printed, published or circulated in the City of Vernon, the City Clerk
is hereby directed to post said notice, or cause the same to be
posted, in three of the most public places in the City of Vernon, to
wit: the northwest corner of 38th Street and Santa Fe Avenue, the
northeast corner of Leonis Boulevard and Pacific Boulevard, and on the
bulletin board in the lobby of the City Hall of the City of Vernon,
located at 4305 Santa Fe Avenue, in said City.
SECTION 5: The City Clerk of the City of Vernon is hereby
directed to post said notice forthwith and the first posting of said
notice shall be at least ten (10) days before the opening of the bids
for the proposed contract. Said notice shall provide that sealed
proposals or bids will be received by the City of Vernon at the office
of the City Clerk, or his designee, at the City Hall, 4305 Santa Fe
Avenue, Vernon, CA 90058-0805.
- 2 -
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
SECTION 6: The City Clerk of the City of Vernon shall
certify to the passage of this resolution, and thereupon and
thereafter the same shall be in full force and effect.
APPROVED AND ADOPTED this 15th day of October, 2003.
ATTEST:
BRUCE V. MALKENHORST, City Clerk
C
EONIS C. MALB RG, Ma or
t
- 3 -
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
STATE OF CALIFORNIA )
) ss
COUNTY OF LOS ANGELES )
I, BRUCE V. MALKENHORST, City Clerk of the City of Vernon,
do hereby certify that the foregoing Resolution, being Resolution No.
8296, was duly adopted by the City Council of the City of Vernon at a
regular meeting of the City Council duly held on Wednesday,
October 15, 2003, and thereafter was duly signed by the Mayor of the
City of Vernon.
(SEAL)
Zf===v
BRUCE V. MALKENHORST, City Clerk
- 4 -
EXHIBIT
0
CITY OF VERNON LIGHT AND POWER
Specification No. GS1-2003
1.0 SCOPE
This specification outlines the requirements for a three phase, group operated, 60 Hz
Resettable Fault Interrupter (RFI) switch utilizing Sulfur Hexafluoride (SF6) switches for
load interruption and SF6 vacuum breaker switches for fault interruption tested to ANSI
C37.71 or ANSI C37.60 featuring deadfront, compact, sealed, corrosion resistant
construction for vault/subsurface installations.
In comparing proposals or bids, consideration will not be confined to price only. The successful
bidder will be one whose product is judged to best serve the interests of the City of Vernon
when price, product, safety, quality and delivery are considered. The City of Vernon reserves
the right to reject any or all proposals or bids or any part thereof, and to waive any minor
technicalities from the specifications. A contract will be awarded to the bidder submitting the
lowest responsible bid meeting the requirements of this specification.
A. General
The RFI shall have two (2) switch positions and three (3) protective (fault interrupter)
positions as shown in Attachment A, Five Position S176 Gas Switch Configuration.
The RFI shall include welded flange 200Amp deepwell on the fault interrupter ways
and 600 Amp apparatus bushings on the switched positions per ANSI/IEEE 386.
(Bolted and gasketed bushings are not acceptable). Attachment A shows the one -line
diagram indicating the circuit configuration, number of switched ways, and type of
bushings required. The switched position shall be located on either end and the
resettable protective positions shall be in the middle. The switch shall be sized to fit
through a 4' x 5' foot vault opening.
The RFI shall be furnished factory filled with an electrical grade of non -toxic, non-
flammable SF6 gas, conforming to ASTM D-2472. A pressure gauge, that provides
visual status of the insulating dielectric, shall be included.
The completed unit shall be capable of withstanding internal failure without explosion
or fire and shall be capable of being mounted in any position for best cable training and
operation.
B. Switch Construction
The RFI shall use deadfront, compact, sealed construction. A corrosion -resistant
stainless steel tank shall enclose the contact system, interconnecting bus, operating
mechanisms, and bushings. The switch must be maintenance free, all welded
construction, eliminating the use of gasketed seals. T.I.G. inert gas welding with
stainless steel filler rod shall be used to eliminate pinhole leaks and corrosion.
3of10
CITY OF VERNON LIGHT AND POWER
Specification No. GS1-2003
The operating shafts must be sealed by a flexible stainless steel bellows (O-ring seals
are not acceptable).
Unless otherwise specified, cable connections, and operating accessories shall be
located so only single side access is required for operation and installation. Operating
handles shall be capable of being removed and stored or permanently attached.
Movement of the operating handles will actuate an internal spring mechanism causing
the switch/interrupter contacts to open or close and latch into position in quick make
quick break operation. The spring operator will use compression springs for long life
and will provide positive position indication.
The switch contacts and interconnecting bus shall be plated copper with Belleville
washers and locking fasteners to provide consistent pressure at bolted connections. The
contacts shall be self -aligning, wiping type, incorporating tungsten copper arcing tips to
prevent wear. The load interrupters use a puffer contact system for fast arc extinction.
A special internal absorbent shall be used for improved performance and to prevent arc
by-products.
The RFI shall incorporate vacuum technology and be capable of interrupting fault
currents up to the rated maximum. The interrupter shall use a flux shifter for tripping
and be manually resettable with no consumable parts. (i.e. fuses). As a safety
precaution, the interrupter will incorporate a trip -free mechanism to prevent the
possibility of holding the interrupter closed under a faulted condition, with no reaction
through the switch handle.
The RFI mechanism shall be a true three-phase group operated device with no
mechanical link between phases. An overcurrent condition on any phase will initiate
the interrupter to trip open all three phases. The RFI interrupter shall also act as a
three-phase, group operated loadbreak switch.
A viewing window with indication of the interrupter contact position shall be provided.
C. Trip Controls
Overcurrent sensing shall be accomplished with an electronic trip control. The controls
shall use current transformers external to the tank to sense the load currents. The
current transformers will provide power to the electronic trip control. No external
power shall be required. Per ANSI/IEEE C57.13, the current transformers shall be
relay accurate class C200 with ratios of 600:0.5A for 600 Amp positions and 200:0.5A
for 200 Amp protective positions. In order to provide immunity to system voltage
disturbances (i.e. transients) the control will not be sensitive to system voltage
conditions. The control shall be fully operable and meet the specified time -current
curves when energized. Trip controls shall be either a vacuum fluorescent type display
(VFD) selection or rotary dial.
4of10
CITY OF VERNON LIGHT AND POWER
Specification No. GS1-2003
If providing a rotary selector switch, the selector switch control shall be used for 200
amp maximum loads. There shall be 10 fuse selections ranging from 30 to 200 amps.
LED indication will be provided to show cause of the last trip simulating a S&C SM-20
"E" type fuse curve. An intermittently blinking LED shall be furnished to indicate
ready status.
The vacuum fluorescent display (VFD) shall be legible at —40°C without the need for a
heater (Operating range —40°C to +65°C). The external current transformers on the
switch will energize the display, when load current is flowing. In the event the switch
is de -energized, a 9V-lithium battery shall be included to allow operation of the display
and keypad for data gathering and parameter setting. The keypad shall be used to select
the following parameters: TCC fuse curves, TCC fuse ratings, instantaneous trip,
ground fault pick-up, ground fault delay and'protection mode. The VFD shall display
the above data as well as the cause of trip. The electronic control shall have the ability
to store up to 64 different TCC curves. Trip selection to be available in 12 positions
from 10 to 450 amps.
Instantaneous trip values shall be in multiples of 1.5 -12 times the current transformer's
primary ratings in increments of 50% of the current transformer primary rating with
values from 300A to 7200A. Ground fault trip settings shall range from 10-30% of the
current transformer primary rating in increments of 5% of the current Transformer
primary rating. Ground fault time delay shall be selectable in 10 settings from .05 to
1.0 seconds.
A RS232 port shall be provided for communication with external devices.
Status contacts for remote SCADA indication shall be provided. A manual trip push-
button for electrically tripping the interrupter shall be provided, with provision for
remote trip.
A RS232 communication port shall be provided to read real time current and fault
current.
Status contacts for remote SCADA indication shall be provided. A manual trip push-
button for electrically tripping the interrupter shall be provided, with provision for
remote trip.
5of10
CITY OF VERNON LIGHT AND POWER
Specification No. GS1-2003
D. Electrical Ratings And Standards:
The switches and/or interrupter shall be designed, tested and built per applicable
sections of ANSI C37.72, ANSI C37.71 and ANSI C37.60 Standards. The assembled
switch assembly shall be rated as shown in Table 1, below.
Table 1. RFI Ratings
SWITCH
RFI
Maximum Design Voltage, KV
15.5
15.5
BIL Impulse Withstand, KV
95
95
Open Gap BIL Flashover Withstand, KV
200
95
One Minute AC Withstand, KV
35
35
Fifteen Minute DC Withstand, KV
66
53
Load Interrupting, Amps
600
600
Asymmetrical Momentary & Three Operation
Fault Close, KA.
_(Optional Ratings)
22.5
(32.40)
19.2
Symmetrical One Second Rating, KA.
(Optional Ratings)
15
(20,25)
12
Continuous Current, A.
600
600
Overload Interrupting Capability, A
3,000
12,000
E. Standard Components
The switch shall have the following standard components:
1 Removable operating handles with padlock provision in the open and closed
position, capable of operation by hotstick or rope with direction of movement
clearly indicated.
2. Stainless steel nameplates providing information including ratings, contact position
indication, circuit configuration and phase identification.
3. Color coded pressure gauge for visual indication of normal operating range,
enclosed in a protective housing to prevent damage.
4. Viewing window that provides fault interrupter position status.
5. Brass fill valve for field addition of SF6 protected and sealed with a removable cap.
6. Clamp type ground lugs, one for each set of bushings.
7. Stainless steel switch tank for maximum corrosion resistance.
8. 200 Amp deepwell on Protective Positions and 600 Amp apparatus welded
bushings on switched positions with protective shipping caps.
9. Lifting and mounting provisions.
6of10
CITY OF VERNON LIGHT AND POWER
Specification No. GSI-2003
F. Optional Features to be provided:
The switch shall have the following optional features:
1. Visible break with contacts visible through viewing windows.
2. Visible break by external neon voltage indicator lights.
3. Operating handle orientation adapters.
4. Fault interrupter remote status.
5. Low pressure sensing device.
6. Operation counter.
7. Manual switching with remote cable operator.
8. Six wall mounted parking stands.
G. Factory Production Tests
100% production testing shall include a mass spectrometer leak test, contact resistance,
mechanical operation, AC one minute withstand and corona extinction tests as well as
bulk SF6 moisture content.
H. Cable Entrances
Switches will include 200Amp deepwell and 600A apparatus welded bushings as
required per ANSFIEEE 386.
2.0 DATA TO BE FURNISHED WITH BID
A. Price, F.O.B. Soto Yard, 2800 Soto Street, Vernon California, 90058.
B. Two sets of dimension, and outline drawings.
C. Instruction manual for care and handling during storage.
D. Delivery schedule
E. Warranty conditions.
7of10
CITY OF VERNON LIGHT AND POWER
Specification No. GS1-2003
3.0 CONTRACT
The vendor shall be required to execute a purchase contract with City of Vernon, and shall
be required to furnish proof of insurance pursuant to Attachment B, Insurance Schedule.
The vendor shall provide a letter from.its insurance company that certifies the amounts of
the insurance policy. The letter from the insurance company will be in substantially the
same form as the SAMPLE INSURANCE FORM LETTER, which is also included in
Attachment B.
4.0 SHIPMENT
A. Supplier shall notify City 48 hours prior to delivery. All delivery shall be Monday -
Friday, 7:30 AM to 3:00 PM.
B. 30 days prior to shipment, supplier shall furnish certified Test reports of the switch.
C. 30 days prior to shipment, supplier shall furnish three (3) sets of Operations/Instruction
Manuals.
5.0 WARRANTY
Supplier shall provide warranty for a minimum of twenty-four (24) months after delivery.
8of10
CITY OF VERNON LIGHT AN6POWER '
Specification No. GS1-2003
ATTACHMENT B
INSURANCE SCHEDULE (Vendor)
The Contractor shall provide proof of insurance, including a standard certificate of insurance, in
at least the following amounts and coverage (combined single limit permitted):
I. Coverage and Limits
Hazards
Automobile Liability
Owned Automobiles
Hired Automobiles
Non -Owned Automobiles
Workers' Compensation
Employers' Liability
II. General Liabilit
Bodily Injury
Each Person Each Accident
$500,000 $1,000,000
$500,000 $1,000,000
$500,000 $1,000,000
$ Statutory
$1,000,000 per employer
Property Damage
Each Accident
$500,000
$500,000
$500,000
Premises Operations
$1,000,000
$2,000,000
$1,000,000
Elevators (if applicable)
$1,000,000
$2,000,000
$1,000,000
Independent Contractors
$1,000,000
$2,000,000
$1,000,000
Products —Completed
$1,000,000
$2,000,000
$1,000,000
Operations
Contractual Liability
$1,000,000
$2,000,000
$1,000,000
Umbrella Liability
$2,000,000
$2,000,000
$2,000,000
1. The general liability policy shall contain the following special endorsements which shall be
noted on or attached to the standard certificate of insurance:
a) An endorsement naming the City of Vernon, its officers, and employees as additional
insureds under the policy.
b) An endorsement providing the City of Vernon thirty (30) days notice of cancellation or
material reduction of coverage.
c) An endorsement providing coverage for all operations under this Contract.
d) Such other endorsement as may be required by addendum hereto.
2. In addition to the standard certificate of insurance, proof of general and umbrella liability
coverage shall be furnished in the form checked below. Only certification of the following
proofs will be accepted:
X For each policy, a notarized letter from the underwriter or carrier certifying that the
coverage and statements in the standard certificate of insurance (attached thereto) are true
and correct and that the signator is an officer authorized to so certify.
A copy of each policy certified by an officer of the underwriter or carrier and notarized.
9 of 10
CITY OF VERNON LIGHT AND POWER
Specification No. GS1-2003
SAMPLE INSURANCE FORM LETTER
(To be issued on insurance carrier letterhead. This letter must be notarized).
Date:
City of Vernon ("City")
4305 Santa Fe Avenue
Vernon, CA 90058
Attn: Risk Management Department
Re: Insurance for City of Vernon
(description ofpermit or contract)
Policy Number(s)
Named Insured:
City Clerk:
I hereby certify that the certificate of insurance attached hereto and made a part hereof by
reference truly and accurately represents the above -cited insurance policies and the insurance
coverage of each for the named insured issued by
(insurance carrier).
The City of Vernon, its officers, and employees are included in said policies as additional
insureds and the City of Vernon will be provided with thirty (30) days written notice of
cancellation or material reduction of coverage.
I certify that I am an officer of the insurance carrier named herein and that I am
authorized to sign this certificate on behalf of said insurance carrier.
Signature
Title
03/03
10 of 10
• ` s
5 4 3 2 1
LINE 1 1 1 LINE 2
P❑SITI❑N
BUSHING RATING (AMPS)
1
600
2
200
3
200
4
200
5
600
N❑TES:
1, SWITCHED P❑SITI❑NS SHALL BE ❑N EITHER SIDE ❑F THE PROTECTIVE P❑SITI❑NS,
2. PR❑TECTIVED P❑SITI❑NS ARE AS SH❑WN,
VERN❑N LIGHT AND P❑WER
SPECIFICATI❑N GS1-2003
FIVE P❑SITI❑N
SF6 GAS SWITCH
1 9/29/03 JL C❑NFIGURATI❑N
N❑ REVISI❑N DATE APPV'D CHK BY ATTACHMENT A
SUPPORTING
DOCUMENTS
8z°' Q
AFFIDAVIT OF POSTING
STATE OF CALIFORNIA )
COUNTY OF LOS ANGELES) ss
CITY OF VERNON )
I, �--- , of the City
of Vernon do hereby certify that I did, on the 4th of
November 2003, post three (3) copies of:
Notice Inviting Sealed Proposals (Bids) for
Bid 41431 (1) Sulfur Hexaflouride (SF6) Gas Vault
Switch for the Light and Power Department
One in each of the following places, to wit: on the
bulletin board in the lobby of the City Hall of the City of
Vernon located at 4305 Santa Fe Avenue; at the northwest
corner of 38th Street and Santa Fe Avenue; the northeast
corner of Leonis Blvd. and Pacific Blvd., all in said City,
there being no newspaper of general circulation printed and
published in the City of Vernon.
Date: r\,I 6�o-,3
State of California )
)ss
County of Los Angeles)
On ,before
Personally appeared S'/1(� 01/N �p�nulSav�
Personally known to me to be the person(o)'whose name('
is/are subscribed to the within instrument and acknowledged
to me that die/she/t-4e-y executed the same in his/her/t-he-i-r
authorized capacity, and that by -ems/her/-t-he4-r signature ('W�
on the instrument the person(, or the entity upon behalf
of which the person( acted, executed the instrument.
WITNESS my hand and official seal
ti to
t.
tos A ci..5 County
IVhl Cc +n n. C�as"23, 2M4
AFFIDAVIT OF POSTING
STATE OF CALIFORNIA )
COUNTY OF LOS ANGELES) ss
CITY OF VERNON )
I , -<* tee- '-,,;,,.. -L-- c'h Ste" _ , of the City
of Vernon do hereby certify that I did, on the 16th of
October 2003, post three (3) copies of:
Notice Inviting Sealed Proposals (Bids) for
Bid 41430 (2) TVI 3-Line Hazardous Materials
Decontamination Shelter Systems for the Fire
Department
One in each of the following places, to wit: on the
bulletin board in the lobby of the City Hall of the City of
Vernon located at 4305 Santa Fe Avenue; at the northwest
corner of 38th Street and Santa Fe Avenue; the northeast
corner of Leonis Blvd. and Pacific Blvd., all in said City,
there being no newspaper of general circulation printed and
published in the City of Vernon.
Date:
State of California )
) ss
County of Los Angeles)
Onm3before me, Ct1&*1,1 L)
Personally appeared
Personally known to me to be the person X whose name(
is/ -awe subscribed to the within instrument and acknowledged
to me that -he/she/t iey executed the same in hzi-s/her/the-i-r
authorized capacity, and that by es/her/-their signature,K
on the instrument the person X, or the entity upon behalf
of which the person �K) acted, executed the instrument.
WITNESS my hand and official seal
M I VALE L+Ef_A
Ccmmu 7cn i 1261903 Z
< < Notary Pubic - CaMomia >
i
3, Los An,e`vs County
My Comm. %ice May 23, 2004
AFFIDAVIT OF POSTING
STATE OF CALIFORNIA )
COUNTY OF LOS ANGELES) ss
CITY OF VERNON )
I , L , :Tch � ,ram. , of the City
of Vernon do hereby certify that I did, on the 15th of
October 2003, post three (3) copies of:
Notice Inviting Sealed Proposals (Bids) for
Bid #1429 (19) Padmount Transformers for the Light &
Power Department
One in each of the following places, to wit: on the
bulletin board in the lobby of the City Hall of the City of
Vernon located at 4305 Santa Fe Avenue; at the northwest
corner of 38th Street and Santa Fe Avenue; the northeast
corner of Leonis Blvd. and Pacific Blvd., all in said City,
there being no newspaper of general circulation printed and
published in the City of Vernon.
�a
Date: kl� k.1(13
State of California )
) ss
County of Los Angeles)
On -, \I-e v►11� �`� :%Zbo3 before me, YYjp 4} Na� 6.
Personally appeared
Personally known to me to be the person N whose nameCoi
is/-a-� subscribed to the within instrument and acknowledged
to me that 4ie/she/t4ey executed the same in -h4-s/her/t-h1e-i7r
authorized capacity, and that by 4i-s/her/their signature XJ
on the instrument the person X), or the entity upon behalf
of which the person X acted, executed the instrument.
WITNESS my hand and official seal
S VALENZUELA
r omrn�ss+cn 1261OG3 L
NotGry ub� ;c - Ca
+ ifomin >
"7 Los Angeles County
Cc-nm.Fxf-kesMay 23,2004
BID RESULTS
BID:
OPENING DATE:
DESCRIPTION:
VENDORS
1. CANADIAN POWER
(c/o Banes Associates)
2. G & W VAULT SF6 SWITCHES
(c/o Banes Associates)
3. ERMCO TRANSFORMERS
(c/o McAvoy & Markham)
4. ALSTOM T & D, Inc.,
(c/o McAvoy & Markham)
5. COOPER POWER SYSTEMS
(c/o Utility Products)
*Sales tax not included
(� L) 0
#1431 V/
NOVEMBER 18, 2003
(1) SULFUR HEXAFLOURIDE (SF6)
GAS VAULT SWITCH
BID TOTAL*
$30,990.00
$31,887.00
No bid
No bid
No bid